Primary Power
120 / 220VAC + 10% -15%, 60 / 50 Hz |
Programmable Relays
Type : Form C
No of Relays : 3
Relay Contact Rating : 2A @ 30 VDC,
0.5A @ 125VAC. |
Standby Power
24V D.C (2 No’s of 12V, 40 Ah (Max), Built in for 12Ah)
Sealed Lead acid battery |
Signaling Line Circuits
Loop card : 4 Nos. Maximum.
No Devices per loop : 254
Loop resistance : 40Ω (Max.).
Loop capacitance : 0.6 µf (Max.).
Loop Current : 300mA (Max.). |
Charging Circuit Charging Voltage 28 V, ±0.2V Nominal
Charging Current 1.2A (Max.). |
Initiating Device Circuits
Class B Style B/C Operation.
No of Conventional Zone : 1
Normal Operating Voltage : 14 – 21 VDC.
Alarm Current : 15 – 30mA.
Short Circuit Current : 45mA Maximum.
Loop resistance : 100Ω Maximum.
End-Of-Line Resistor : 4K7, 1/2watt
Standby Current : 7mA (2mA for Detectors) |
Notification Appliance Circuits
No of circuits : 2
Class B, Style – Y wiring
Operating Nominal Voltage : 24 VDC Nominal
Current for NACs :
NAC – 1 : 0.9A
NAC – 2 : 0.9 A
Line Drop : 2.4V
End-Of-Line Resistor : 4K7, ½ watt
D.C. Output
Supervised 24VDC, 300mA Max. |
Programmable Input Circuit
Normal Operating Voltage : 4 – 8 VDC.
Short Circuit Current : 3mA Maximum.
Loop resistance : 100Ω Maximum.
End-Of-Line Resistor : 4K7, 1/2watt
Standby Current : 1.25mA |