ELECTRICAL SPECIFICATION

Operating Voltage : 17 ~ 28V DC
Reset Voltage : less than 5V
Start-Up Current : 800 µA.
Start-Up Time : less than 30s
Alarm Current : 7 mA.
Reset Time : less than 30s.
Sampling Time : less than 1s.
Remote Output : 2mA maximum open collector
Thermal Rating : 59 °C (138 °F)
Rate of Raise of Temp : 11.1 °C / min (20° F/min)
Smoke Sensitivity : 0.09 dB/m ~ 0.14 dB/m.
Operating Temperature : -10 °C to 50 °C
Humidity : 0 – 95% RH, non-condensing

MECHANICAL SPECIFICATION

Height : 46 mm with base
Diameter : 100 mm dia
Weight : 150g with base
IP Rating : IP – 42

COMPATIBLE DEVICE

Models Description
RE-374B Detector Normal Base
RE-374BI Detector Isolator Base
MonitI Addressable Single Loop FACP

ORDERING INFORMATION

Model Description
RE-337SH Analogue Addressable Photoelectric & Heat Detector

FEATUES

  • Complies with EN 54.
  • Dual LED’s for 360° visibility.
  • Advanced detection and communication protocol.
  • Stable photoelectric smoke sensing chamber. No adjustment or replacement required
  • Polarity Insensitive.
  • Easy installation and maintenance.
  • Sleek low-profile housing design.
  • Regular 100mm base.
  • Simple Soft address programming for Easy installation.