Operating Voltage | : | 24VDC |
Quiescent Current | : | 80 mA |
Alarm Current | : | 130mA |
Operating Condition | ||
Operating Temperature | : | 0-49° C/32-120° F. |
Relative Humidity | : | 93 ± 2% RH (non-condensing) at 32 ±2° C/ 90 ±3° F. |
Operating Condition | ||
Type | : | Form C |
No of Relays | : | 1 |
Relay Contact Rating | : | 2A @ 30 VDC,
0.5A @ 125VAC |
Mechanical Specification
Dimensions | : | (350W X 300H X 90D)mm | |
Color | : | White / Red / Black | |
Construction | : | 18 Gauge (1.22 mm) CRCA sheet with powder-coated Finish | |
IP Rating | : | IP50 | |
Cable Entry | : | 9xø19mm Knockout in top of the cabinet 9xø22.25mm Knockout in top of the cabinet | |
Weight | : | 5Kg |
Compatible Devices
MODEL | DESCRIPTION |
---|---|
Avani | Analogue Addressable Fire Alarm Control Panel |
Ordering Information
MODEL | Description |
---|---|
AVANI-RP-W/B/R | Analogue Addressable Fire Alarm Repeater Panel |
Note :
W – White Color
R – Red Color
B – Black Color
Peer to Peer Networking
Terminal Diagram
The Avani-RP repeater panel is a compact remote unit for Ravel-Avani Intelligent Analogue Addressable fire Alarm panel. It repeats all the indications of FACP in standalone or in network Panel. It has (40X4) 160 character LCD Display. This repeater is connected to Avani FACP using RS 485 communication network. Any communication fault or any loss in communication due to cable fault is indicated in this repeater panel. The display parameters can be selected individually to suit the requirement of each remote area.